Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 8
10Table 4 — Capacity Control Reduction StepsCapacity Control Pressure (Fig. 8)LOADED OPERATION — Pressure-operated control valveis controlled by suc
11LEGENDFig. 11 — Compressor(Bottom Plate Removed)1—Oil Pressure Relief Valve5—Eccentric Shaft2—Piston and Eccentric Strap Assembly6—Eccentric Strap S
12SERVICEService Notes1. Where compressor components are shown, they are innormal order of removal from compressor.2. For replacement items, use Carri
13PHASE BARRIERPOSITIONINGKEY (SEE FIG. 19)87 6 5 43 26 2212019181716151413121191012524232244 42 41 16 38 37 36 3546454748 49 271539404334 33 32 31 30
14LEGEND FOR FIG. 12Cylinder Heads — Disassemble cylinder heads by re-moving cap screws and prying up on side between cylinderhead and valve plate to
15Suction and Discharge Valve Plate Assembly(Fig. 16) — Test for leaking discharge valves by pumpingcompressor down and observing suction and discharg
16Cleaning Suction Strainer1. Pump down compressor.2. Remove motor end cover and screws holding disc typestrainer (Fig. 18) to cover.3. Clean strainer
17PUMP END MAIN BEARING — This bearing is a ma-chined part of the new aluminum oil pump and bearing headcasting. Disassemble bearing head. If bearing
18TROUBLESHOOTING LEGENDTXV — Thermostatic Expansion ValveRead Safety Considerations on page 1 before proceedingwith troubleshooting.PROBLEM CAUSE RE
19 LEGENDTXV — Thermostatic Expansion ValvePROBLEM CAUSE REMEDYSystem noises.Piping vibration. Support piping as required, check for loose pipe conne
2Fig. 1 — 07D Condensing Unit DimensionsDIMENSIONS (in.)UNIT 07D WIDTH AA20330B20530A208399/16B210519/16B212519/16B2156313/16WATER CONNECTIONS FOR 07D
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.PC 8
3Fig. 2 — 06D Compressor Unit DimensionsNOTES:1. For standard service practices, such as trouble-shooting and refrigerant charging, allow a minimum2′-
4Install a solenoid valve (field supplied) in liquid line directlybefore expansion valve. Solenoid valve is necessary for singlepumpout control used o
5Fig. 3 — Unit Label Diagram — 06D,07D UnitsAUX —AuxiliaryC—Compressor ContactorCH —Crankcase HeaterCR —Control RelayDX —Direct ExpansionEQUIP —Equipm
6Compressor Unit Connections — Extend power leads fromcontrol center (contactor terminals) to compressor terminal boxand make connections as shown in
7Fig. 6 — Recommended Field WiringLEGENDAUX —AuxiliaryOL —Overload RelayC—ContactorPOR —Pumpout RelayCR —Control RelaySW —SwitchHPS —High-Pressure Swi
8Refrigerant ChargingEVACUATE, DEHYDRATE AND LEAK TEST — Entire re-frigerant system must be evacuated, dehydrated and leak testedby methods described
9Table 2A — 06D Physical Data*Compressors listed are for R-22 applications. For R-134a and R-507/404A an 06DR compressor is standard. Factory compress