Copyright 2001 Carrier Corporation Form 50TFQ-C3PD
Single-package standard efficiency
rooftop heat pumps with:
State-of-the-art defrost system
Dependable 4-way valve operation
Refrigerant filter strainer and
accumulator
Field-installed electric heaters
available
Advanced hermetic compressors
mounted on vibration isolators
Factory-installed Apollo communi-
cating controls, non-fused discon-
nect switch available
Features/Benefits
The 50TFQ standard
efficiency rooftop product
line combines advanced
technology with
serviceability, performance,
and flexibility.
State-of-the-art defrost system
uses time and temperature to keep the
outdoor coil frost-free for economical,
dependable operation.
Dependable 4-way valve opera-
tion safely and efficiently accomplish-
es cycle reversals, defrost, and normal
operation.
Refrigerant filter strainer and ac-
cumulator ensure performance
dependability and circuit protection.
Field-installed electric heaters
available in a wide range of capaci-
ties. Single-point wiring kit makes
installation simple.
NOTE: Some electric heater applica-
tions not available for use with
factory-installed disconnect switch.
50TFQ008-012
Single-Package
Standard Efficiency
Rooftop Heat Pump Units
50 Hz
Nominal Capacities: 26.4 to 35.2 kW
(7
1
/
2
to 10 Nominal Tons)
Product
Data
50TFQ008-012
Vista de página 0
1 2 3 4 5 6 ... 39 40

Resumo do Conteúdo

Página 1 - Features/Benefits

Copyright 2001 Carrier Corporation Form 50TFQ-C3PDSingle-package standard efficiencyrooftop heat pumps with:• State-of-the-art defrost system• Dependa

Página 2 - Table of contents

10Accessory dimensionsCONNECTORPKG.ACCY.BCD ALTDRAINHOLEGAS POWER CONTROLCRBTMPWR001A002′-87/16″[827]1′-1015/16″[583]13/4″[44.5]3/4″[19] NPT3/4″ [19]

Página 3 - Model number nomenclature

11I Determine cooling and heating requirementsat design conditions.Given:Required Cooling Capacity (TC) . . . . . . . . . 23 kWSensible Heat Capacity

Página 4 - Physical data (SI)

12I Determine cooling and heating requirementsat design conditions.Given:Required Cooling Capacity (TC) . . . . .78,000 BtuhSensible Heat Capacity (SH

Página 5 - Physical data (English)

13COOLING CAPACITIESLEGENDNOTES:1. Ratings are gross, and do not account for the effects of the indoor-fan motor power and heat.2. Direct interpolatio

Página 6 - Options and accessories

14COOLING CAPACITIES (SI) (cont)LEGENDNOTES:1. Ratings are gross, and do not account for the effects of the indoor-fan motor power and heat.2. Direct

Página 7

15COOLING CAPACITIES (SI) (cont)LEGENDNOTES:1. Ratings are gross, and do not account for the effects of the indoor-fan motor power and heat.2. Direct

Página 8 - DURABLADE ECONOMIZER

16COOLING CAPACITIES (ENGLISH)LEGENDNOTES:1. Ratings are gross, and do not account for the effects of the indoor-fan motor power and heat.2. Direct in

Página 9 - Base unit dimensions

17COOLING CAPACITIES (ENGLISH) (cont)LEGENDNOTES:1. Ratings are gross, and do not account for the effects of the indoor-fan motor power and heat.2. Di

Página 10 - Accessory dimensions

18INSTANTANEOUS AND INTEGRATED HEATING RATINGS (SI)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instantaneous) capac

Página 11 - (with 50TFQ008 example) — SI

19INSTANTANEOUS AND INTEGRATED HEATING RATINGS (SI) (cont)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instantaneous

Página 12

2Easy conversion from vertical to horizontal discharge to make retro-fit and add-on jobs easier. To convert from vertical to horizontal discharge, sim

Página 13 - Performance data

20INSTANTANEOUS AND INTEGRATED HEATING RATINGS (SI) (cont)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instantaneous

Página 14 - Performance data (cont)

21INSTANTANEOUS AND INTEGRATED HEATING RATINGS (ENGLISH)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instantaneous)

Página 15

22INSTANTANEOUS AND INTEGRATED HEATING RATINGS (ENGLISH) (cont)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instanta

Página 16

23INSTANTANEOUS AND INTEGRATED HEATING RATINGS (ENGLISH) (cont)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instanta

Página 17

24FAN PERFORMANCE (SI) — VERTICAL DISCHARGE UNITSLEGENDNOTES:1. Boldface indicates field-supplied drive required.2. indicates field-supplied motor and

Página 18

25FAN PERFORMANCE (SI) — HORIZONTAL DISCHARGE UNITSLEGENDNOTES:1. Boldface indicates field-supplied drive required.2. indicates field-supplied motor a

Página 19

26FAN PERFORMANCE (ENGLISH) — VERTICAL DISCHARGE UNITSLEGENDNOTES:1. Boldface indicates field-supplied drive required.2. indicates field-supplied moto

Página 20

27FAN PERFORMANCE (ENGLISH) — HORIZONTAL DISCHARGE UNITSLEGENDNOTES:1. Boldface indicates field-supplied drive required.2. indicates field-supplied mo

Página 21

28ACCESSORY STATIC PRESSURE DROP (Pa)50TFQ008-012ACCESSORY STATIC PRESSURE DROP (in. wg)50TFQ008-012FAN R/S AT MOTOR PULLEY SETTINGS (SI)FAN RPM AT MO

Página 22

29INDOOR-FAN MOTOR PERFORMANCELEGEND*Extensive motor and electrical testing on these units ensures that the full BkW (or brake horse-power) range of t

Página 23

3Ratings summaryLEGENDNOTE: Ratings are net values adjusted for the effects of indoor-fan motor heat. Ratings are based on:Cooling Standard: 27 C (80

Página 24

30LEGEND*Heaters are field installed only.†Used to determine minimum disconnect per NEC (U.S.A. Standard).**Heater capacity (kW) is based on heater vo

Página 25

31Typical piping and wiringHORIZONTAL DISCHARGE DUCTINGVERTICAL DISCHARGE DUCTINGLEGENDNEC — National Electrical Code (U.S.A.)

Página 26

32Operating sequenceCooling, units without economizer — When the ther-mostat calls for cooling, terminals G and Y1 are energized.The indoor-fan contac

Página 27

33If Y1 is energized, and the compressor no. 1 is alreadyenergized (see Step 2) and the room thermostat calls forY2, compressor no. 1 continues to ope

Página 28

34Typical wiring schematic

Página 29 - MULTIPLICATION FACTORS

35LEGEND AND NOTES FOR TYPICAL WIRING SCHEMATICAHA — Adjustable Heat AnticipatorAWG — American Wire GageC—Contactor, CompressorCAP — CapacitorCB — Cir

Página 30 - Electrical data

36Outdoor installation — Units approved for outdoorinstallation only.Ductwork — Secure vertical discharge ductwork to roofcurb. For horizontal dischar

Página 31 - Typical piping and wiring

37Packaged Rooftop Air-to-Air Heat Pumpwith Electric Heat Option — ConstantVolume ApplicationHVAC Guide SpecificationsSize Range: 26.4 to 35.2 kW (71/

Página 32 - Controls

384. Filters shall be accessible through an accesspanel with ‘‘no-tool’’ removal.H. Controls and Safeties:1. Unit Controls:a. Unit shall be complete w

Página 33

39preset to admit up to 50% outdoor air for year-round ventilation.* 6. 100% Two-Position Damper:a. Two-position damper package shall includesingle bl

Página 34 - Typical wiring schematic

4LEGENDAl — Aluminum*Indoor coil fin material/outdoor coil fin material.†Weight of 356 mm roof curb.NOTE: The 50TFQ units have a loss-of-charge/low-pr

Página 35

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.New

Página 36 - Application data

5LEGEND*Indoor coil fin material/outdoor coil fin material.†Weight of 14-in. roof curb.NOTE: The 50TFQ units have a loss-of-charge/low-pressure switch

Página 37 - Guide specifications

6*Factory installed.†Field installed.**Accessory single-point kit is required for size 008-012 units using electric heat.ITEM OPTION* ACCESSORY†Apollo

Página 38 - Guide specifications (cont)

7HCELECTRIC HEATERElectric heaters are available in a wide rangeof capacities for field installation.THERMOSTATZone thermostat (24 v) provides one- or

Página 39

8Options and accessories (cont)MINIMUMPOSITIONOPEN31TPP1T1425SSODCTRBREV.B198818A%HUMIDITY9070603010DCBA6065707555508580DAMPERDAMPERCLOSEDOPENOUTDOOR

Página 40

9Base unit dimensionsUNIT50TFQSTANDARDUNITWEIGHTECONOMIZERWEIGHT(DURABLADE)CORNERWEIGHT(A)CORNERWEIGHT(B)CORNERWEIGHT(C)CORNERWEIGHT(D)“H” “J”“K”Lb Kg