Copyright 2001 Carrier Corporation Form 50TFQ-C3PDSingle-package standard efficiencyrooftop heat pumps with:• State-of-the-art defrost system• Dependa
10Accessory dimensionsCONNECTORPKG.ACCY.BCD ALTDRAINHOLEGAS POWER CONTROLCRBTMPWR001A002′-87/16″[827]1′-1015/16″[583]13/4″[44.5]3/4″[19] NPT3/4″ [19]
11I Determine cooling and heating requirementsat design conditions.Given:Required Cooling Capacity (TC) . . . . . . . . . 23 kWSensible Heat Capacity
12I Determine cooling and heating requirementsat design conditions.Given:Required Cooling Capacity (TC) . . . . .78,000 BtuhSensible Heat Capacity (SH
13COOLING CAPACITIESLEGENDNOTES:1. Ratings are gross, and do not account for the effects of the indoor-fan motor power and heat.2. Direct interpolatio
14COOLING CAPACITIES (SI) (cont)LEGENDNOTES:1. Ratings are gross, and do not account for the effects of the indoor-fan motor power and heat.2. Direct
15COOLING CAPACITIES (SI) (cont)LEGENDNOTES:1. Ratings are gross, and do not account for the effects of the indoor-fan motor power and heat.2. Direct
16COOLING CAPACITIES (ENGLISH)LEGENDNOTES:1. Ratings are gross, and do not account for the effects of the indoor-fan motor power and heat.2. Direct in
17COOLING CAPACITIES (ENGLISH) (cont)LEGENDNOTES:1. Ratings are gross, and do not account for the effects of the indoor-fan motor power and heat.2. Di
18INSTANTANEOUS AND INTEGRATED HEATING RATINGS (SI)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instantaneous) capac
19INSTANTANEOUS AND INTEGRATED HEATING RATINGS (SI) (cont)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instantaneous
2Easy conversion from vertical to horizontal discharge to make retro-fit and add-on jobs easier. To convert from vertical to horizontal discharge, sim
20INSTANTANEOUS AND INTEGRATED HEATING RATINGS (SI) (cont)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instantaneous
21INSTANTANEOUS AND INTEGRATED HEATING RATINGS (ENGLISH)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instantaneous)
22INSTANTANEOUS AND INTEGRATED HEATING RATINGS (ENGLISH) (cont)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instanta
23INSTANTANEOUS AND INTEGRATED HEATING RATINGS (ENGLISH) (cont)LEGENDNOTES:1. indicates integrated ratings.2. Integrated capacity is maximum (instanta
24FAN PERFORMANCE (SI) — VERTICAL DISCHARGE UNITSLEGENDNOTES:1. Boldface indicates field-supplied drive required.2. indicates field-supplied motor and
25FAN PERFORMANCE (SI) — HORIZONTAL DISCHARGE UNITSLEGENDNOTES:1. Boldface indicates field-supplied drive required.2. indicates field-supplied motor a
26FAN PERFORMANCE (ENGLISH) — VERTICAL DISCHARGE UNITSLEGENDNOTES:1. Boldface indicates field-supplied drive required.2. indicates field-supplied moto
27FAN PERFORMANCE (ENGLISH) — HORIZONTAL DISCHARGE UNITSLEGENDNOTES:1. Boldface indicates field-supplied drive required.2. indicates field-supplied mo
28ACCESSORY STATIC PRESSURE DROP (Pa)50TFQ008-012ACCESSORY STATIC PRESSURE DROP (in. wg)50TFQ008-012FAN R/S AT MOTOR PULLEY SETTINGS (SI)FAN RPM AT MO
29INDOOR-FAN MOTOR PERFORMANCELEGEND*Extensive motor and electrical testing on these units ensures that the full BkW (or brake horse-power) range of t
3Ratings summaryLEGENDNOTE: Ratings are net values adjusted for the effects of indoor-fan motor heat. Ratings are based on:Cooling Standard: 27 C (80
30LEGEND*Heaters are field installed only.†Used to determine minimum disconnect per NEC (U.S.A. Standard).**Heater capacity (kW) is based on heater vo
31Typical piping and wiringHORIZONTAL DISCHARGE DUCTINGVERTICAL DISCHARGE DUCTINGLEGENDNEC — National Electrical Code (U.S.A.)
32Operating sequenceCooling, units without economizer — When the ther-mostat calls for cooling, terminals G and Y1 are energized.The indoor-fan contac
33If Y1 is energized, and the compressor no. 1 is alreadyenergized (see Step 2) and the room thermostat calls forY2, compressor no. 1 continues to ope
34Typical wiring schematic
35LEGEND AND NOTES FOR TYPICAL WIRING SCHEMATICAHA — Adjustable Heat AnticipatorAWG — American Wire GageC—Contactor, CompressorCAP — CapacitorCB — Cir
36Outdoor installation — Units approved for outdoorinstallation only.Ductwork — Secure vertical discharge ductwork to roofcurb. For horizontal dischar
37Packaged Rooftop Air-to-Air Heat Pumpwith Electric Heat Option — ConstantVolume ApplicationHVAC Guide SpecificationsSize Range: 26.4 to 35.2 kW (71/
384. Filters shall be accessible through an accesspanel with ‘‘no-tool’’ removal.H. Controls and Safeties:1. Unit Controls:a. Unit shall be complete w
39preset to admit up to 50% outdoor air for year-round ventilation.* 6. 100% Two-Position Damper:a. Two-position damper package shall includesingle bl
4LEGENDAl — Aluminum*Indoor coil fin material/outdoor coil fin material.†Weight of 356 mm roof curb.NOTE: The 50TFQ units have a loss-of-charge/low-pr
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.New
5LEGEND*Indoor coil fin material/outdoor coil fin material.†Weight of 14-in. roof curb.NOTE: The 50TFQ units have a loss-of-charge/low-pressure switch
6*Factory installed.†Field installed.**Accessory single-point kit is required for size 008-012 units using electric heat.ITEM OPTION* ACCESSORY†Apollo
7HCELECTRIC HEATERElectric heaters are available in a wide rangeof capacities for field installation.THERMOSTATZone thermostat (24 v) provides one- or
8Options and accessories (cont)MINIMUMPOSITIONOPEN31TPP1T1425SSODCTRBREV.B198818A%HUMIDITY9070603010DCBA6065707555508580DAMPERDAMPERCLOSEDOPENOUTDOOR
9Base unit dimensionsUNIT50TFQSTANDARDUNITWEIGHTECONOMIZERWEIGHT(DURABLADE)CORNERWEIGHT(A)CORNERWEIGHT(B)CORNERWEIGHT(C)CORNERWEIGHT(D)“H” “J”“K”Lb Kg