10Step 4 — Complete Refrigerant PipingConnectionsUse field-supplied refrigerant grade piping designed for usewith R-410A refrigerant.FLARING THE ENDS
11Step 5 — Make Electrical Connections See Tables 6A and 6B for electrical information.UNITS WITH ELECTRIC HEATER — The unit is equippedwith two ther
12Room ControllerConnectionsGroundConnectionOutdoor UnitConnectionsLowVoltageHighVoltagePowerConnectionsFig. 21 — 40KMC Unit Matched to 38HDF Outdoor
13LowVoltageHighVoltageRoom ControllerConnectionsOutdoor UnitConnectionsPowerConnectionsGroundConnectionFig. 22 — 40KMQ Unit Matched to 38HDF Outdoor
14LowVoltageHighVoltageRoom ControllerConnectionsGroundConnectionOutdoor UnitConnectionsPowerConnectionsFig. 23 — 40KMQ Unit Matched to 38QRF Outdoor
15ETTESSAC LABOLG CMK04RESNEDNOC ROODTUO FDH83NOTE 6NOTE 5NOTE 4YALPSIDRIA-MTLIOC-MT"D" RALUDOMBCP1 LORTNOCREPPOC ERABTCENNOCSID TINU OT)DED
16ETTESSAC LABOLG QMK04RESNEDNOC ROODTUO FDH83NOTE 6NOTE 5YALPSIDRIA-MT LIOC-MT"D" RALUDOMBCP1 LORTNOCREPPOC ERABTCENNOCSID TINU OT)DE
17ETTESSAC LABOLG QMK04RESNEDNOC ROODTUO FRQ83NOTE 6NOTE 5YALPSIDRIA-MT LIOC-MT"D" RALUDOMBCP1 LORTNOCREPPOC ERABTCENNOCSID TINU OT)DE
18INTERNAL CONTROL PANEL40KMC018C apacitorG MC boardE lectric heater board(only on models with electric heater)TransformerHoles for fixing panel in p
19WIRING THE ROOM CONTROLLER — The room con-troller is capable of controlling from 1 to 6 fan coil units. Thetotal run length of the wire connecting
2INSTALLATIONStep 1 — Complete Pre-Installation ChecksUNPACK UNIT (See Fig. 1) — Move the unit to final loca-tion. The grille panel and the remote con
204.72”(120)ØA BØA Ø CDuct connection flangeClip1/4" (6 mm) neoprene gasketInsulated flexible ductFresh air intakeConditioned air supply to anad
21Room Controller Configuration Setup — To con-figure the room controller, press the Mode button for 5 sec-onds. After 5 seconds, “10” will appear. T
22Louver Mode Selection — To enter louver modeselection, ensure the room controller is on and then press theFan button for 5 seconds. After 5 seconds,
23Any of the following will cancel the Service Test mode:• When the unit is turned off by the controller.• If the power is cycled during the Test Mode
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
32'-4-11/32"(720)1'-9-21/32"(550))515("23/98-'11-7/8"(47)1'-11-7/16"(595))318("8-'2)069("4
4Table 4A — 40KMC Physical Data LEGEND*See Table 3 for factory charge and additional field charge requirements.SYSTEM SIZE 018 0
5Table 4B — 40KMQ Physical Data LEGEND*See Table 3 for factory charge and additional field charge requirements.SYSTEM SIZE 0
6Step 2 — Locating and Mounting the UnitLOCATING THE UNIT — Install the unit as centrally aspossible in the room. The air flow direction can be contro
7The condensate may be discharged at a maximum height of77/8 in. above the unit, as long as the ascending tube is verticaland aligned with the drainag
8Step 3 — Locating and Mounting the RoomControllerLOCATING THE ROOM CONTROLLER — See Fig. 14for room controller dimensions. If the air sensor in the
9MOUNTING THE ROOM CONTROLLER (Fig. 15-17) —Unscrew the side fixing screw. Open the room controller rearmounting base to expose the mounting holes. Th