Table 1 Thermostat Wiring Terminations
EXISTING
WIRE
DESIGNATION
FUNCTION
TERMINAL
CONNECTION
GorF Fan G
Y1, Y, or C Cooling Y1
W1, W, or H Heating W1/O/B
Rh, R, M, Vr, or A Power (24 v) R
C Common C*
O/B Reversing Valve W1/O/B†
Y2 Second Stage Cooling Y2*
W2 Second Stage Heating W2*
*Terminals C, W2, and Y2 may not be used in all applications.
†Used on Heat Pump applications only.
Set Clock The Set Clock button allows the user to change
the time and day displayed on the thermostat. Press the Set
Clock button. The current time will blink on and off. Press
the UPARROW and DOWN ARROW buttons until the cor-
rect time is shown. Hold down the buttons to quickly move
through the time display. The AM and PM annunciators will
automatically change. Hold down the Fan button while press-
ing UP ARROW or DOWN ARROW to change the time by
hours instead of minutes. To ensure the schedules are prop-
erly followed, make sure that AM or PM is correct for the
time chosen. When the correct time is shown, press the Mode
button to modify the day of the week. The current day will
blink on and off. Press the UP ARROW and DOWN AR-
ROW buttons until the correct day is shown. Press the Set
Clock button again to exit the Set Time mode.
Heat Pump Configuration To configure the ther-
mostat for heat pump operation,Advanced Setup Steps 3 (Heat
Pump Operation) and 4 (Reversing Valve Polarity) must be
configured correctly. See the Configure Advanced Setup sec-
tion for information on configuring these options.
NOTE: Some large commercial rooftop heat pump units
(50HJQ,TJQ,EJQ) must be configured with Advanced Setup
Step 3 (Heat Pump Operation) set to OFF. Refer to the base
unit instructions for more information.
Configure Advanced Setup To enter into the ad-
vanced setup screens of the thermostat, press the Mode and
Program buttons at the same time. The Advanced Setup Step
number is shown in the top right corner of the thermostat
screen. Use the Mode button to advance through the steps.
There are 15 Advanced Setup Steps. See Table 2. Press the
Program button at any time to exit the Advanced Setup mode.
NOTE: Advanced Setup Steps 1 and 2 are configured with
the Set Clock button, and are not accessed through the ad-
vanced setup screens.
HEAT PUMP CONFIGURATION (Steps 3 and 4) To set
the thermostat for heat pump operation, Advanced Setup
Step 3 must be configured to ON. Use the UP and DOWN
ARROW buttons to configure the step. The default is OFF.
Press the mode button to continue to Step 4. Step 4 is used
to set the reversing valve polarity for the heat pump. The
variable can be set to either ‘B’’or ‘O.’ Set the reversing
valve polarity to the correct value depending on the appli-
cation. The default is ‘O.’
NOTE: Step 4 will appear only if Step 3 is set to ON.
Step 5 will appear only if Step 3 is set to OFF.
ELECTRIC HEAT CONFIGURATION (Step 5) Step 5
is used to configure the thermostat for electric heat. The vari-
able can be configured ON or OFF. The default is OFF.
NOTE: Step 5 will appear only if Step 3 is set to OFF.
Table 2 Advanced Setup Configuration
STEP DESCRIPTION RANGE DEFAULT
1* Time of Day
12:00 AM -
11:59 PM
12:00 AM
2* Day of the Week
Sunday through
Saturday
Monday
3 Heat Pump Off/On Off
4
Reversing Valve
Polarity
O/B O
5 Electric Heat Off/On Off
6 Deadband 1 - 6 degrees 2
7
Forced Minimum
Temperature Difference
0 - 6 degrees 2
8 Cycles per Hour d, d1,2-6 6
9 Thermoglow™ Backlight Off/On On
10
Reset Service
Filter Icon
——
11
Service Filter
Run Time
0-1950 hrs 500 hrs
12 Temperature Units F/C F
13 Security Level 0 - 3 0
14
Maximum Allowable
Heat Set Point
35 - 99 F (1-37 C) 80 F (27 C)
15
Minimum Allowable
Cooling Set Point
35 - 99 F (1-37 C) 65 F (18 C)
*Accessed and configured through the Set Clock button.
W2
TYPICAL
UNIT
L
C
G
Y1
E
O
W1
R
Y2
24 VAC COMMON
FAN RELAY
COMPRESSOR RELAY
1st STAGE HEAT CIRCUIT
24 VAC RETURN
2nd STAGE HEAT CIRCUIT
W2
Y2
R
W1
Y1
G
C
THERMOSTAT
B
O
Fig.3—Typical Wiring (Single-Stage Cooling Units)
W2
TYPICAL
UNIT
L
C
G
Y1
E
O
W1
R
Y2
24 VAC COMMON
FAN RELAY
COMPRESSOR RELAY
1st STAGE HEAT CIRCUIT
24 VAC RETURN
2nd STAGE COMPRESSOR RELAY
2nd STAGE HEAT CIRCUIT
W2
Y2
R
W1
Y1
G
C
THERMOSTAT
B
O
Fig.4—Typical Wiring (Two-Stage Cooling Units)
3