Carrier 17/19EX Especificações Página 139

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 138
Inspect Wiring
1.
Examine wiring for conformance to job wiring diagrams and to all applicable electrical
codes.
2.
On low-voltage compressors (600 v or less) connect voltmeter across the power wires to
the compressor starter and measure the voltage. Compare this reading with the voltage
rating on the compressor and starter nameplates.
3.
Compare the ampere rating on the starter nameplate with the compressor nameplate. The
overload trip amps must be 108% to 120% of the rated load amps.
Do not check voltage supply without proper equipment and precautions. Serious
injury may result. Follow power company recommendations.
WARNING
!
WARNING
CAUTION
CAUTION
!
Do not apply any kind of test voltage, even for a rotation check, if the machine is
under a dehydration vacuum. Insulation breakdown and serious damage may
result.
Vista de página 138
1 2 ... 134 135 136 137 138 139 140 141 142 143 144 ... 436 437

Comentários a estes Manuais

Sem comentários