Carrier 19XL Especificações Página 19

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 80
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 18
To Separate Cooler and Condenser
1. Turn vessel separation feet into lowered position (Figure 5, Item 1).
2. Disconnect the flared fitting on the refrigerant motor cooling line at the isolation valve
(Figure 6, Item 3).
3. Disconnect the condenser discharge line at the compressor (Figure 6, Item 1).
4. Cut the hot gas bypass line on the cooler side of the isolation valve (not shown).
5. Cut cooler liquid feed line at location indicated (Figure 5, Item 2).
6. Cover all openings.
7. Disconnect the wires and cable housings which cross from the starter to the power panel at
the power panel (Figure 7, Item 8).
Click here for Table 4 — Additional Heat Exchanger Weight for Marine Waterboxes*
Click here for Table 5A 19XL Waterbox Cover Weights* (English, lb.)
Click here for Table 5B 19XL Waterbox Cover Weights* (SI, kg)
Vista de página 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 79 80

Comentários a estes Manuais

Sem comentários