Mixed-Air Temperature (MAT) Sensor -- The mixed-air
temperature sensor is a 3 K thermistor located at the discharge
of the indoor fan. The sensor is mounted through the side plate
of the blower The sensor is a probe and has blue leads. This
sensor is factory installed. The operating range of temperature
measurement is 0° to 158 E
Outdoor Air Lockout Sensor -- The EconoMi$er IV is
equipped with a temperature limit switch located in the outdoor
airstream which is used to lock out the compressol,s below a
50 F ambient temperature.
ECONOMI$ER IV CONTROLLER WIRING AND OPER-
ATIONAL MODES -- Determine file EconoMi$er IV control
mode before inst_ling sensol_ and accessories. Diffelent sensol_
ale required for different control modes, and a number of
accessories m_eav_dlable. Refer to _tble 3. The EconoMiSer IV
is supplied from the factory with a mixed air temperature
sensor and an outdoor air temperatme sensor. This _dlows for
operation of the EconoMiSer IV with outdoor air dry bulb
changeover control. Additional accessories can be added to
allow for different types of changeover control and operation
of the EconoMiSer IV and unit. See Fig. 14 for wiring.
Outdoor Dry Bulb Changeover -- The stan&trd controller is
shipped from the factory configmed for outdoor dry bulb
changeover control. The outdoor<dr and mixed-air temperature
sensors are included as stan&trd. For this control mode, the out-
door tempel_tture is comptu_ed to an adjustable set point selected
on the control. If the outdoor-air temperature is above the set
point, the EconoMi$er IV will adjust the outside air d_tmpel_ to
minimum position. If the outdoor-air tempel_ture is below the
set point, the position of the outside _tir dampers will be con-
trolled to provided free cooling using outdoor air. When in this
mode, the LED next to the free cooling set point potentiometer
will be on. The changeover temperature set point is controlled
by the free cooling set point potentiometer located on the con-
troL The scale on the potentiometer is A, B, C, and D. See
Fig. 15 for the conesponding temperature changeover values.
Differential Dry Bulb Control -- For differential cay bulb
control the stan&trd outdoor dry bulb sensor is used in conjunc-
tion with an additional accessory ca-y bulb sensor (part number
CRTEMPSN002A00). The accessory sensor must be mounted
in the return _drstream. Connect the return air temperature
sensor to the SR terminal (after lemoving the 620-ohm lesistor)
and to the + terminal on the controllel: See Fig. 16.
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower tempera-
turn ttir stmtu_l is used for cooling. When using this mode of
changeover control, turn the enthalpy set point potentiometer
fully clockwise to the D setting. See Fig. 17.
Outdoor Enthalpy Changeover -- For enthalpy control, ac-
cessory enth_flpy sensor (part number HH57AC078) is
required. Replace the standard outdoor dry bulb temperature
sensor with the accessory enthalpy sensor in the stu_le mount-
ing location. When the outdoor air enthalpy rises above the
outdoor enth_dpy changeover set point, the outdoor<dr dtu_lper
moves to its minimum position. The outdoor enth_dpy
changeover set point is set with the outdoor enthalpy set point
potentiometer on the EconoMi$er [V controller The set points
tue A, B, C, and D. See Fig. 18. The factory-inst_dled 620-ohm
jumper must be in place across terminals SR and + on the
EconoMi$er IV controllel: See Fig. 16.
Differential Enthalpy Control -- For differential enthalpy
control, the EconoMi$er IV controller uses two enfllalpy sen-
sors (CRENTDIF004A00), one in the outside air and one in the
return air duct. The EconoMi$er IV controller compares the
outdoor air enthalpy to the return air enth_dpy to determine
EconoMi$er IV use. The controller selects the lower enth_dpy
ttir (return or outdoor) for cooling. For example, when the out-
door _fir has a lower enthalpy than the return ail: the
EconoMi$er IV opens to bring in outdoor tdr for free cooling.
Replace the stan&trd outside air d U bulb temperature sensor
with the accessoq enthalpy sensor in the same mounting loca-
tion. Mount the return air enthalpy sensor in the return air duct.
The return air enth_flpy sensor is wiled to terminals SR and + on
the EconoMi$er IV controllel: See Fig. 16. The outdoor
enthalpy changeover set point is set with the outdoor enthalpy
set point potentiometer on the EconoMi$er IV controllel: When
using this mode of changeover control, turn the enthalpy set
point potentiometer fully clockwise to the D setting.
BL8
TB1 1Q>_ }_ ...............
/BI S/O P 4 5 P [GRA
PL_ 7
.................................................;BRN
ECONOMIZER
NOTOR
ECONOMIZERACCY/FIOP
PL5 3
RED_RED \\
\
\
\\\
\_ OAS IS D]SCOSN_CTED w_8_ ACCY
OA ENTBAL_X iS INSTA{LED
?ECI
PEC2
>ECB
Fig. 14 J EconoMi$er IV Wiring
23