5
LEGEND
*Air Conditioning & Refrigeration Institute.
NOTES:
1. Standard ratings are net values, reflecting the effects of circulating fan heat.
Supplementary electric heat is not included. Ratings are based on:
Cooling Standard:
80 F db, 67 F wb (wet bulb) indoor entering-air temper-
ature and 95 F db entering-air outdoor unit.
Hi-Temp Heating Standard:
70 F db (dry bulb) indoor entering-air temper-
ature and 47 F db/43 F wb entering-air outdoor unit.
Lo-Temp Heating Standard:
70 F db indoor entering-air temperature and
17 F wb/15 F db entering-air outdoor unit.
38AQS008, 012 and 40RMQ008, 012 are rated in accordance with current
ARI Standard 210/240. 38AQS016 and 40RMQ016 are rated in accordance
with current ARI Standard 340/360. Unit combinations are rated in accor-
dance with ARI standard 210/240 or 340/360 as appropriate.
2. Sound ratings are in accordance with current ARI Standard 270.
3. 38AQS012,016 are connected to 40RMQ024,028 in duplex configurations.
OUTDOOR
UNIT
38AQS
INDOOR
UNIT
40RMQ
AIRFLOW
(Cfm)
COOLING
HEATING
SOUND
RATING
(decibels)
Hi-Temp Low-Temp
Net Cap.
(Btuh)
EER IPLV
Net Cap.
(Btuh)
COP
Net Cap
(Btuh)
COP
008
008 3,000 86,000 9.8 N/A 83,000 3.0 46,000 2.0 92
012
012 4,000 108,000 8.9 11.2 111,000 3.0 62,000 2.0 88
016
016 6,000 172,000 8.8 9.9 164,000 3.0 94,000 2.2 88
012,012
(Duplex)
024 8,000 216,000 8.8 10.6 222,000 2.8 124,000 1.8 —
012,016
(Duplex)
028 10,000 280,000 8.8 9.6 275,000 2.8 156,000 1.9 —
Bels —
Sound Level (1 bel = 10 decibels)
COP —
Coefficient of performance =
Btuh output
or
Btuh input
Btuh output
(Based on ARI conditions)
Unit Power Input x 3.413
EER —
Energy Efficiency Ratio =
Btuh
(Based on ARI conditions)
Unit Power Input
IPLV —
Integrated Part-Load Value
ARI* capacities