Carrier operating and maintanance Instruções de Operação Página 19

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 41
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 18
19
Side 1 and 2: Cut the connection profiles to the
correct length and mount them on the correct side
(see Fig 44).
Side 3: Cut the connection profile to the correct
length and mount it on the correct side (see Fig
37).
Side 4: Cut the connection profile to the correct
length and mount it on the correct side (see Fig
47).
• Mount Z-profiles over the projecting cross beam of
the top section as shown in Fig. 48 of this chapter.
The plastic roof foil of the bottom casing section can
be applied over these profiles.
7. FRESH AIR INLET HOOD
The fresh air inlet hood may be supplied loose with the
AHU. In this case the air inlet hood must be attached
in the correct position as follows:
Install the inlet hood with the screws supplied in the
correct location.
The bottom wire grille should then be attached to
the corner post.
Figure 46.
- Fresh air inlet hood
NOTE: The connection between the outdoor
air suction grille and the corner post should be
sealed.
8. ROOF COVER
For outdoor installations the roof cover should be
provided with a finish. If the casing section has a flat
top use one of the following two methods:
Method 1
Shorten the plastic roof foil strip supplied to the
correct length. Ensure that the strip projects enough
to attach it to the side of the roof edge with a blow
dryer.
Ensure that the roof cover already attached to the
two casing sections to be connected is clean and
dust-free.
Attach the roof cover strip with a blow dryer over the
entire length of the joint up to the roof edge.
Remove any excess roof foil up to the underside
of the roof edge.
Figure 47.
- Roof finish. method 1
Figure 48.
- Roof finish. method 2
Method 2
Fix sealing tape to the connection profiles. Drill 160
mm holes with a 10 mm diameter through the con-
nection profiles. Be sure to remove the drill shavings
after drilling.
Attach the casing sections to each other using bolts
and nuts (M8).
Seal the seam on the top of the connectiong pro-
files.
SEAL
M8x25 BOLT
DIN 933
SEALING TAPE 6x15 mm
UNIT 1
ÜNİTE 2
SEAL
M8x25 BOLT
DIN 933
SEALING TAPE 6x15 mm
UNIT 1
ÜNİTE 2
PVC SIZDIRMAZLIK
BANTI 6x15
UNIT 2
UNIT 2
6x15
6x15