10Control Wiring — The PremierLink controller can beconnected to either a Carrier-approved thermostat or CCNcompatible temperature sensor.1. Turn off
11Table 3 — Thermistor Resistance vs Temperature Values for Space Temperature Sensor,Supply Air Temperature Sensor, andOutdoor Air Temperature SensorW
124-20mAFig. 12 — PremierLink™ Controller and Sensor Wiring — 33ZCT55SPT and 33ZCT56SPT Space Temperature Sensors;33ZCSENSAT Supply Air Temperature Se
13d. In the control box, install a no. 10 ring type crimplug on the shield drain wire. Install this lug underthe mounting screw of the PremierLink con
14Perform the following steps if state or local code requiresthe use of conduit, or if the installation requires a cable lengthof more than 8 ft:1. Se
15321J5321J5321J4J312+-24 VACDEDICATED 24 VACTRANSFORMERSEE NOTE 1SEE NOTE 2Fig. 16 — PremierLink™ Controller Wiring — Combination Temperature and CO2
16AC- / DC-AC+ / DC+THERM +THERM -COM4 - 20 mA0-5 / 10 VDC18-42 VDC18-30 VACBLUBRNBRNBLUREDFig. 17 — PremierLink™ Controller Wiring — Combination Temp
17 HUMIDITY SENSOR (WALL-MOUNTED) INSTALLA-TION — The accessory space humidity sensor is installed onan interior wall to measure the relative humidit
184-20mANOTE: Remove BROWN wire from J5-3 and insert into J5-4.Fig. 21 — Humidity Sensor Wiringa33-9212
19OUTDOOR AIR TEMPERATURE SENSOR (Fig. 22-25) —The OAT sensor must be located properly. For outdoor loca-tions use sensor 33ZCSENOAT. For duct mountin
2GENERALThe PremierLink™ controller, version 3.x, is a field retrofitrooftop control compatible with the Carrier Comfort Network®(CCN) system. This co
20SINGLE-GANGALUMINUMBELL BOX0.5000 IN.(12.7 mm) NPTTHREADEDCONDUITOPENINGS TYP.GROUNDSCREW4.9200 IN.(125.0 mm)4.5625 IN.(115.9 mm)2.8125 IN.(71.4 mm)
21Fig. 26 — PremierLink™ Factory-Installed Controller Wiring for R-22 Units (48/50TM,TF,HJ,HE003-014and 50TFQ,HJQ,HEQ003-012)a33-899CONTROLBOARDROOFTO
22 4-20mANOTE: Remove red wire from J4-9 to prevent 24 VAC shorting out other components or ground.Fig. 28 — PremierLink™ Field-Installed Controller
23Enthalpy Switch/Receiver — The accessory en-thalpy switch/receiver (33CSENTHSW) senses temperatureand humidity of the air surrounding the device
24 4-20mAFig. 31 — Typical Wiring Schematic — Carrier Rooftop Unit with PremierLink™ Controls*Used with Differential Enthalpy Control only.a33-921
25Mount the enthalpy sensor in a location where the indoor aircan be sampled (such as the return air duct). The enthalpysensor is not a NEMA 4 enclosu
26NOTE: If installing in a Carrier rooftop, use the two graywires provided from the control section to the economizerto connect PremierLink™ controlle
274-20mANOTE: If PremierLink™ controller is grounded and actuator is grounded on common side, then common wire from PremierLink controller J9-2 isnot
28Economizer with 4 to 20 mA Actuator — ThePremierLink controller can be connected to an economizer.The economizer features a Johnson 4 to 20 mA
295 4 3 2 1VDC0-10DAFIXED—mA2-10RAAUTO6-9MOVE TO LEFTFOR 4-20mA CONTROLWITH PREMIERLINKCONTROLLERFig. 39 — Position of Actuator Mode Switches(
3conjunction with the return air enthalpy sensor(33CSENTSEN) to measure both indoor and outdoor enthalpyand to determine which is greater. The enthalp
30START-UPUse the Carrier network communication software to start upand configure the PremierLink controller.Changes can be made using the ComfortWORK
31input cannot be used, so any fire/life safety shutdown must bephysically wired to disable the 24 vac control circuit to the unit.Indoor Fan — The in
32minimum damper position will become 0 and the IQMP =MDP. IAQ mode will resume when the SAT > SASP – 8° F inheating or the SAT < SASP + 5° F i
33Table 7 — Available Cooling Stages * If conditions are suitable for economizer operation.After a compressor is locked out, it may be started again a
34The Maximum SHSR is determined by the SATHI configu-ration. If the supply-air temperature exceeds the SATHI config-uration value, then the heat stag
35• SPT reading is available• OAT reading is available• Enthalpy is low• OAT > NTLO (with 1 degree F hysteresis) and < Max FreeCool set pointIf
36For more information on how the PremierLink controller isused in conjunction with the Carrier 3V control system, contactyour CCN controls representa
37Outside Air Sensor Failure — A flashing asterisk near thesensor value in the display table. The following functions willbe disabled:• Unoccupied fre
38Table 11 — Points Display (STATUS1)NOTE: Bold values indicate points that can be forced through communications.SUPPLY FAN STATUS — This point disp
39When configured for a remote door switch, if the point isON, then the heating and cooling outputs will be turned off af-ter a configured time delay.
4PWRHS3/EXH/RVSHS2HS1CMP2CMP1FANREDORNPNKWHTBLUYELGRNBRNREDREDCUT FOR DUALTRANSFORMEREQUIPMENTRELAYSCUT TOISOLATECONTROLLERPOWERPWRJ1J8RY1Y2W1W2GCX48H
40COMPRESSOR SAFETY — When the controller is insensor mode, this point can be used to monitor the status of thecompressor trouble output supplied
41Table 12 — Thermostat Control Input Display (CV_STAT)NOTE: Bold values indicate points that can be forced through communications.Table 13 — Alarm Se
42Manual OverrideHours: Units hoursRange 0 to 4Default Value 0 OCCUPANCY SCHEDULE — For flexibility of scheduling,the occupancy programming is broken
43Unoccupied Heating Deadband: Units delta degrees F(delta degrees C)Range 0.0 to 10.0 Default Value 1.0UNOCCUPIED COOLING DEADBAND — The Unoccu-p
44Range 40.0 to 60.0Default Value 50.0STAGED COOLING — The staging function is used for DXcooling (1 or 2 stages). The staging function uses the cool
45NOTE: In thermostat mode, the modulation may appear toregularly change. However, it will precisely control leaving-airtemperature.The economizer Sta
46The IAQ Pre-Occupancy Purge Algorithm shall use thisvalue for the minimum damper position whenever Outdoor AirTemperature is below Unoccupied OAT Lo
47Default Value 2.0COMPRESSOR TIME GUARD FOR FIRE SHUT-DOWN — When the Fire Shutdown point is active, the supplyfan is immediately shut down. The comp
48the controller will respond to when a broadcast for Redline/Loadshed has been detected on the CCN bus. Loadshed GroupNumber: Range 1-16Default Value
49FILTER TIMER HOURS — The Filter Timer Hours config-uration determines when the filter status will display a “Dirty”alarm. When the Filter Timer Hour
5PWRHS3/EXH/RVSHS2HS1CMP2CMP1FANREDORNPNKWHTBLUYELGRNBRNREDREDCUT FOR DUALTRANSFORMEREQUIPMENTRELAYSCUT TOISOLATECONTROLLERPOWERPWRJ1J8RCRHW1W2Y1Y2GC5
50CURRENT OCCUPIED PERIOD — If the controller is con-figured to determine occupancy locally, the Current OccupiedPeriod point is used to display the c
51THERMOSTAT CONTROL — Indicates the result of theconfiguration decision to control in the thermostat or sensormode.ThermostatControl: Display Range N
52the number of required stages. When in the thermostat mode,the value displayed is zero.Cool SubmasterReference: Display Units degrees F (degrees C)
53Table 21 — Primary Maintenance Screen (MAINT)NOTE: Bold values indicate points that can be forced through communications.Average Unoccupied Cool Set
54Table 22 — System Pilot™ Maintenance Table (SP_MAINT)NOTE: Bold values indicate points that can be forced throughcommunications.ROOFTOP MODE — This
55HEATING PERCENT TOTAL CAPACITY — The Heat-ing Percent Total Capacity point is used to display the currentHeating Capacity. When heat is enabled, th
56APPENDIX A — STATUS, CONFIGURATION AND MAINTENANCE SCREENSTable A — Points DisplayLEGENDSPT — Space Temperature SensorNOTE: Bold values indicate poi
57APPENDIX A — STATUS, CONFIGURATION AND MAINTENANCE SCREENS (cont)Table C — Alarm Service ConfigurationLEGENDIAQ — Indoor Air QualityNOTE: Bold value
58APPENDIX A — STATUS, CONFIGURATION AND MAINTENANCE SCREENS (cont)Table H — PremierLink™ Control ConfigurationLEGENDNOTE: Bold values are configurabl
59APPENDIX A — STATUS, CONFIGURATION AND MAINTENANCE SCREENS (cont)Table K — Primary Maintenance Screen (MAINT)LEGENDNOTE: Bold values indicate points
6Fig. 4 — Typical PremierLink™ Control Wiring to 38AH024-034 Units with Single Air Handler(24 v)(115 v)LEGENDCB — Circuit BreakerEQUIP — EquipmentGND
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata
7Fig. 5 — Typical PremierLink™ Control Wiring to 38AH024-034 Units with 2 Air Handlers1098765432110987654321(24 v)TB2CB3*+CB4+IFC†2CCS2COOL1COOL2COOL1
8Fig. 6 — Typical PremierLink™ Control Wiring to 38AH044-104 UnitsLEGENDCR — Control RelayHD — Heating DeviceIFC — Indoor-Fan ContactorIFR — Indoor-Fa
9Table 1 — PremierLink Controller Inputs and OutputsLEGENDINPUTS POWER TERMINAL(S)SPACE TEMPERATURE (SPT) AI (10K Thermistor) J6-7, J6-6SET POINT ADJU