INSTALLATION
Step 1 -- Plan for Unit Location -- Select a loca-
tion for the unit and its support system (curb or other) that
provides minimum clearances required for safety, unit perfor-
mance and service access below, around and above unit as
specified in unit drawings. Consider also the effect of adjacent
units.
Do not install unit in an indoor location. Do not locate air
inlets near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, guard against water fiom higher
level runoff and overhangs.
Select a unit mounting system that provides adequate height
to allow installation of condensate trap per requirements. Refer
to Step 6 -- Install External Trap for Condensate Drain for
required trap dimensions.
ROOF MOUNT -- Check building codes for weight distribu-
tion requirements. Unit operating weight is shown in Table 1.
Step 2 -- Provide Unit Support
ROOF CURB -- Assemble or install accessory roof curb in
accordance with instructions shipped with this accessory. See
Fig. 1. Install insulation, cant strips, roofing, and counter flash-
ing as shown. DuctwoN can be inst_dled to roof curb before unit
is set in place. DuctwoN must be attached to curb and not to the
unit. Curb must be level. This is necessary to permit unit drain to
fimction properly. Unit leveling tolerance is _+J/l_, in. per linem
fl in any direction. Refer to Accessory Roof Curb Installation
Instructions for additional information as required. When acces-
soU roof curb is used, unit may be installed on class A, B, or C
roof covering materi_d. CmTier roof curb accessories are for flat
roofs or slab mounting.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket with the roof
curb as shown in Fig. 1. Improperly applied gasket can also
result in air leaks and poor unit performance. Do not slide
unit to position on roof curb.
ALTERNATE UNIT SUPPORT- When a curb cannot be
used, install unit on a noncombustible surface. Support unit
with sleepel.s, using unit curb support area. If sleepers c_mnot
be used, support long sides of unit with a minimum of 3 equ_fl-
ly spaced 4-in. x 4-in. pads on each side.
Step 3 -- Rig and Place Unit -- Inspect unit for trans-
portation damage. See Table 1 for physical &_ta. File any claim
with transportation agency.
All panels must be in place when rigging. Damage to unit
may result.
Do not drop unit; keep upright. Use top crate to prevent
sling or cable &_mage. Rollel_ may be used to move unit across
a roof. Level by using unit rail as a reference; leveling tolerance
is + 1/16 in. per linear fl in any direction. See Fig. 2 for addition-
al information. Unit rigging weight is shown in Fig. 2.
Rigging holes are provided in the unit base rails as shown in
Fig. 2. Refer to rigging instructions on unit.
Maintain clearance, per Fig. 3, m'ound and above unit to
provide minimum distance fi_)m combustible materials, proper
airflow, and service access. See Fig. 4 for location on access
panels.
After unit is in position, remove crating and polyethylene
sheet.
INSTALLATION ONTO CURB -- The 50PG units me de-
signed to fit on the accessory full perimeter crab. In either case,
correct placement of the unit onto the curb is critical to operat-
ing performance. To aid in correct positioning, place unit on
roof curb to maintain I/4-in. gap between the inside of rail and
roof curb on long sides and a I/z-in. gap between the inside of
rail and roof curb on both duct and condenser ends. Refer to
Fig. 1 and 3, to assure proper duct opening alignment.
NOTE: Before positioning unit onto curb, refer to Step 6 --
Install External Trap for Condensate Drain section on page 7
concerning bottom di'ain connection plug.
Do not slide unit to position it when it is sitting on the curb.
Curb gasketing material may be ck_maged and leaks may
result.
SLAB MOUNT (Horizontal Units Only) -- Provide a level
concrete slab that extends a minimum of 6-in. beyond unit cab-
inet. Install a grovel apron in front of condenser-coil air inlet to
prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may also be installed on a roof curb if
required.