CONTROL CONTROL POINT
CURVE APPROX. °F (°C)
AT 50% RH
A 73 (23)
B 70 (21)
C 67 (19)
D 63 (17)
85 90 95 100 105 110
(35) (38) (43)
/
/ "Ix/ I "WI I\1
\
_'/3-. Jf \1 A\
";Z
\ 1_/"4_ I \V
\
\
HIGH LIMIT
CURVE
35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
(2) (4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43)
o o
APPROXIMATE DRY BULB TEMPERATURE i F (C)
Fig. 18- Enthalpy Changeover Set Points
6000
5000
z
_o 4000
3000
Z
OO 2000
UJ
(3
z 1000
<
oc
CO2 SENSOR MAX RANGE SETTING
+800 ppm
_9OO ppm
_lOOO ppm
+1100 ppm
2 3 4 5 6 7 8
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Fig. 19 -- 002 Sensor Maximum Range Setting
4. Connect 24 vac across tem]inals TR and TRI.
5. Cmefully adjust the minimum position potentiometer
until file measured mixed air temperature matches the cal-
culated value.
6. Reconnect file mixed-air sensor to terminals T and TI.
Remote control of the EconoMi$er IV damper is desirable
when requiring additional temporary ventilation. If a field-
supplied lemote potentiometer (Honeywell p_ut number
$963B1128) is wired to the EconoMi$er IV controller, the
minimum position of the damper can be controlled from a
remote location.
To control the minimum damper position remotely, remove
the factory-installed jumper on the P and PI terminals on the
EconoMi$er IV controller Wire the field-supplied potentiome-
ter to the P and PI terminals on the EconoMiSer IV controllel:
See Fig. 16.
Damper Movement -- When the EconoMiSer IV board re-
ceives initial power, it can take the damper up to 21/2 minutes
before it begins to position itself. After the initial positioning,
subsequent changes to damper position will take up to 30 sec-
onds to initiate. Damper movement from lull open to full
closed (or vice versa) takes 21/2 minutes.
Thermostats -- The EconoMiSer IV control works with con-
ventional thermostats that have a YI (cool stage 1), Y2 (cool
stage 2), WI (heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMiSer IV control does not support space temperature
sensors. Connections me made at the thermostat terminal con-
nection board located in the main control box.
Pressure Drop -- See Fig. 20 and 21 for EconoMi$er [V pres-
sure drop. Evaporator fan may need to be adjusted.
25