Carrier GTR040-420 Especificações Página 31

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 30
31
When a specific item is located, the item name appears on
the left of the display, the value will appear near the middle of
the display and the units (if any) will appear on the far right of
the display. Press the key at a changeable item and
the value will begin to flash. Use the up and down arrow keys
to change the value, and confirm the value by pressing the
key.
Two items, OAT Outside Air Temperature (Temperature
Mode, Sub-mode UNIT) and SPT Space Temperature (Tem-
perature Mode, Sub-mode UNIT) can be forced to a value at
the Navigator. Use the procedure outlined above to change and
force the value. If one of these two points has been forced, a
flashing f indicating the force will appear next to the value.
To remove the force, select the item. Press the key so
that the value is flashing. Press the up and down arrow keys
simultaneously and the force will be removed.
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to
change the value or state and press the key to accept
it. Press the key to return to the next higher level of
structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are pass-
word protected. The words Enter Password will be displayed
when required, with the default password also being displayed.
Use the arrow keys to change the number and press
to enter the digit. Continue with the remaining digits of the
password. The default password is 1111. The password can
only be changed at the Navigator or through CCN devices such
as ComfortWORKS®, ComfortView and Service Tool.
Adjusting the Contrast
The contrast of the display
can be adjusted to suit ambient conditions. To adjust the con-
trast of the Navigator, press the key until the display
reads, Select a menu item. Using the arrow keys move to the
Configuration mode. Press to obtain access to this
mode. The display will read:
> TEST OFF
METR OFF
LANG ENGLISH
Pressing will cause the OFF to flash. Use the up
or down arrow to change OFF to ON. Pressing
will illuminate all LEDs and display all pixels in the view
screen. Pressing and simultaneously al-
lows the user to adjust the display contrast. The display will
read:
Adjust Contrast
- - - -+ - - - - - - - - - - - - - - -
Use the up or down arrows to adjust the contrast. The
screens contrast will change with the adjustment. Press
to accept the change. The Navigator will keep this
setting as along as it is plugged in to the LEN bus.
Adjusting the Backlight Brightness
The back-
light of the display can be adjusted to suit ambient conditions.
The factory default is set to the highest level. To adjust the
backlight of the Navigator, press the key until the
display reads, Select a menu item. Using the arrow keys
move to the Configuration mode. Press to obtain ac-
cess to this mode. The display will read:
> TEST OFF
METR OFF
LANG ENGLISH
Pressing will cause the OFF to flash. Use the up
or down arrow keys to change OFF to ON. Pressing
will illuminate all LEDs and display all pixels in the
view screen. Pressing the up and down arrow keys simulta-
neously allows the user to adjust the display brightness. The
display will read:
Adjust Brightness
- - - - - - - - - - - - - - - - - +
Use the up or down arrow keys to adjust the brightness. The
screens brightness will change with the adjustment. Press
to accept the change. The Navigator will keep this
setting as long as it is plugged in to the LEN bus.
Service Test (See Table 10)
Both main power and
control circuit power must be on.
The Service Test function should be used to verify proper
operation of compressors, unloaders, hot gas bypass (if in-
stalled), cooler pump and remote alarm relays, EXVs and con-
denser fans. To use the Service Test mode, the Enable/Off/
Remote Contact switch must be in the OFF position. Use the
display keys and Table 10 to enter the mode and display TEST.
Press twice so that OFF flashes. Enter the password if
required. Use either arrow key to change the TEST value to the
ON position and press . Switch the Enable/Off/
Remote Contact switch to the Enable position (Version 2.3 and
later). Press and the button to enter the OUTS
or COMP sub-mode.
Test the condenser fan, cooler pump, and alarm relays by
changing the item values from OFF to ON. These discrete out-
puts are turned off if there is no keypad activity for 10 minutes.
Use arrow keys to select desired percentage when testing ex-
pansion valves. When testing compressors, the lead compres-
sor must be started first. All compressor outputs can be turned
on, but the control will limit the rate by staging one compressor
per minute. Compressor unloaders and hot gas bypass relays/
solenoids (if installed) can be tested with compressors on or
off. The relays under the COMP sub-mode will stay on for
10 minutes if there is no keypad activity. Compressors will stay
on until they are turned off by the operator. The Service Test
mode will remain enabled for as long as there is one or more
compressors running. All safeties are monitored during this test
and will turn a compressor, circuit or the machine off if re-
quired. Any other mode or sub-mode can be accessed, viewed,
or changed during the TEST mode. The MODE item (Run Sta-
tus mode under sub-mode VIEW) will display 0 as long as
the Service mode is enabled. The TEST sub-mode value must
be changed back to OFF before the chiller can be switched to
Enable or Remote contact for normal operation.
Configuring and Operating Dual Chiller Con-
trol (See Tables 19A and 19B)
The dual chiller
routine is available for the control of two units supplying
chilled fluid on a common loop. This control is designed for a
parallel fluid flow arrangement only. One chiller must be con-
figured as the master chiller, the other as the slave chiller. An
additional leaving fluid temperature thermistor (Dual Chiller
LWT) must be installed in the common chilled water piping as
shown in Fig. 21 and connected to the master chiller. See Field
Wiring section for Dual Chiller LWT Accessory sensor control
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
Vista de página 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 103 104

Comentários a estes Manuais

Sem comentários