APPENDIX A — CCN TABLES (cont)
RESETCON (Temperature Reset and Demand Limit)
BRODEFS (Broadcast POC Definition Table)
DESCRIPTION STATUS DEFAULT UNITS POINT
COOLING RESET
Cooling Reset Type 0 = No Reset
1 = 4-20 ma input
2 = External temp-OAT
3 = Return fluid
4 = External temp-SPT
0 CRST_TYP
No Cool Reset Temp 0 to 125 125.0 °FCT_NO
Full Cool Reset Temp 0 to 125 0.0 °FCT_FULL
Degrees Cool Reset –30 to 30 0.0 ^F CT_DEG
HEATING RESET
Heating Reset Type 0 = No Reset
1 = 4-20 ma input
2 = External temp — OAT
3 = Return fluid
4 = External temp — SPT
0 HRST_TYP
No Heat Reset Temp 0 to 125 0.0 HT_NO
Full Heat Reset Temp 0 to 125 125.0 % HT_FULL
Degrees Heat Reset –30 to 30 0.0 min HT_DEG
DEMAND LIMIT
Demand Limit Select 0 = None
1 = External switch input
2 = 4-20 ma input
3 = Loadshed
0DMD_CTRL
Demand Limit at 20 mA 0 to 100 100 % DMT20MA
Loadshed Group Number 0 to 99 0 SHED_NUM
Loadshed Demand Delta 0 to 60 0 % SHED_DEL
Maximum Loadshed Time 0 to 120 60 min SHED_TIM
Demand Limit Switch 1 0 to 100 80 % DLSWSP1
Demand Limit Switch 2 0 to 100 50 % DLSWSP2
LEAD/LAG
Lead/Lag Chiller Enable Enable/Disable Disable LL_ENA
Master/Slave Select Slave/Master Master MS_SEL
Slave Address 0 to 239 0 SLV_ADDR
Lead/Lag Balance Select Enable/Disable Disable LL_BAL
Lead/Lag Balance Delta 40 to 400 168 hours LL_BAL_D
Lag Start Delay 0 to 30 5 mins LL_DELAY
DESCRIPTION STATUS DEFAULT UNITS POINT
CCN Time/Date Broadcast Yes/No No CCNBC
CCN OAT Broadcast Yes/No No OATBC
Global Schedule Broadcast Yes/No No GSBC
CCN Broadcast Acker Yes/No No CCNBCACK
Daylight Savings Start
Month 1 to 12 4 STARTM
Week 1 to 5 1 STARTW
Day 1 to 7 7 STARTD
Minutes to add 0 to 99 60 min MINADD
Daylight Savings Stop
Month 1 to 12 10 STOPM
Week 1 to 5 5 STOPW
Day 1 to 7 7 STOPD
Minutes to subtract 0 to 99 60 min MINSUB