Table 18 — Example of Temperature Reset (Return Fluid) Configuration
NOTE: The example above shows how to configure the chiller for temperature reset based on chiller return fluid. The
chiller will be configured for no reset at a cooler
∆
T (EWT-LWT) of 10 F (5.6 C) and a full reset of 8 F (4.4 C) at a cooler
∆
T
of 2 F (1.1 C).
Table 19A — Example of Configuring Dual Chiller Control (Master Chiller)
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY ITEM EXPANSION COMMENT
RSET CRST 0 COOLING RESET TYPE 0 = No reset
1 = 4 to 20 mA input
2 = Outdoor Air Temp
3 = Return Fluid
4 = Space Temperature
0
Scrolling stops
0
Value flashes
3
Select 3
3
Change accepted
CRST 3
Item/Value/Units scrolls again
CRT1 125 NO COOL RESET TEMP
Range: 0° to 125 F
125
Scrolling stops
125
Value flashes
10
Select 10
10
Change accepted
CRT1 10
Item/Value/Units scrolls again
CRT2 0 FULL COOL RESET TEMP
Range: 0° to 125 F
0
Scrolling stops
0
Value flashes
2
Select 2
2
Change accepted
CRT2 2
Item/Value/Units scrolls again
DGRC 0 DEGREES COOL RESET
Range: –30 to 30 F
0
Scrolling stops
0
Value flashes
8
Select 8
8
Change accepted
DGRC 8
Item/Value/Units scrolls again
SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT
OPT2 CTRL CONTROL METHOD
CTRL 0 SWITCH SCROLLING STOPS
0VALUE FLASHES
3SELECT 3
CTRL 3 CCN CHANGE ACCEPTED
CTRL
CCNA
CCNA 1 CCN ADDRESS DEFAULT 1
CCNA
CCNB
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE