Table 3 LID Screens
IMPORTANT: The following notes apply to all Table 3
examples:
1. Only 12 lines of information will appear on the LID screen at any
given time. Press NEXT
or PREVIOUS to highlight a point, or
to view points below or above the current screen.
2. The LID may be configured in English or Metric units, as required,
through the LID configuration screen.
3. Data appearing in the ‘‘Reference Points Names’’ column is used
for CCN operations only.
4. All options associated with ICE BUILD, LEAD/LAG, CCN OCCU-
PANCY CONFIGURATION, and SOFT STOPPING are only avail-
able in PSIO Software Version 13 and higher.
5. All values shall be variables available for read operation from
a CCN Network. Descriptions designated (*) shall support write
operations for BEST programming language, data transfer, and
overriding.
EXAMPLE1—STATUS01 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS
(STATUS01 will be highlighted).
3. Press SELECT
.
DESCRIPTION RANGE UNITS REFERENCE POINT NAME
Control Mode Reset, Off, Local, CCN MODE
Run Status Timeout, Recycle, Startup, Ramping, Running, Demand, STATUS
Override, Shutdown, Abnormal, Pumpdown
Occupied ? No/Yes OCC
Alarm State NORMAL/ALARM ALM
*Chiller Start/Stop STOP/START CHIL S S
Base Demand Limit 40-100 % DLM
*Active Demand Limit 40-100 % DEM LIM
Compressor Motor Load 0-999 % CA L
Current 0-999 % CA P
Amps 0-999 AMPS CA A
*Manual Slide Valve Count −20-20 SV MAN
Actual Slide Valve State Increase, Hold, Decrease SV ACT
Water/Brine: Setpoint 20-120 (−6.7-48.9) DEG F (DEG C) SP
* Control Point 20-120 (−6.7-48.9) DEG F (DEG C) LCW STPT
Entering Chilled Water −40-245 (−40-118) DEG F (DEG C) ECW
Leaving Chilled Water −40-245 (−40-118) DEG F (DEG C) LCW
Entering Condenser Water −40-245 (−40-118) DEG F (DEG C) ECDW
Leaving Condenser Water −40-245 (−40-118) DEG F (DEG C) LCDW
Evaporator Refrig Temp −40-245 (−40-118) DEG F (DEG C) ERT
*Evaporator Pressure 6.7-420 (−46-2896) PSI (kPa) ERP
Condenser Refrig Temp −40-245 (−40-118) DEG F (DEG C) CRT
*Condenser Pressure 6.7-420 (−46-2896) PSI (kPa) CRP
Discharge Temperature −40-245 (−40-118) DEG F (DEG C) CMPD
Rotor Inlet Temp −40-245 (−40-118) DEG F (DEG C) RTRIN
Motor Winding Temp −40-245 (−40-118) DEG F (DEG C) MTRW
Oil Sump Temperature −40-245 (−40-118) DEG F (DEG C) OILT
*Oil Pressure Transducer 6.7-420 (−46-2896) PSI (kPa) OILP
Oil Pressure 6.7-420 (−46-2896) PSID (kPad) OILPD
Line Voltage: Percent 0-999 % V P
Actual 0-9999 VOLTS V A
*Remote Contacts Input OFF/ON REMCON
Total Compressor Starts 0-65535 c starts
Starts in 12 Hours 0-8 STARTS
Compressor Ontime 0-500000 HOURS c hrs
*Service Ontime 0-32767 HOURS s hrs
*Compressor Motor kW 0-9999 kW CKW A
EXAMPLE2—STATUS02 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press STATUS
.
3. Scroll down to highlight STATUS02.
4. Press SELECT
.
DESCRIPTION
POINT TYPE
UNITS REFERENCE POINT NAME
Input Output
Slide Valve Increase X OFF/ON SV INC
Slide Valve Decrease X OFF/ON SV DEC
Hot Gas Bypass Relay X OFF/ON HGBR
*Chilled Water Pump X OFF/ON CHWP
Chilled Water Flow X NO/YES EVFL
*Condenser Water Pump X OFF/ON CDP
Condenser Water Flow X NO/YES CDFL
Compressor Start Relay X OFF/ON CMPR
Compressor Start Contact X OPEN/CLOSED 1CR AUX
Compressor Run Contact X OPEN/CLOSED RUN AUX
Starter Fault Contact X OPEN/CLOSED STR FLT
Pressure Trip Contact X OPEN/CLOSED PRS TRIP
Single Cycle Dropout X NORMAL/ALARM V1 CYCLE
Variable Inlet Relay X OFF/ON VIR
Oil Heater Relay X OFF/ON OILH
Oil Safety Sensor X OPEN/CLOSED OILSS
*Tower Fan Relay X OFF/ON TFR
Compr Shunt Trip Relay X OFF/ON TRIPR
Alarm Relay X NORMAL/ALARM ALM
Spare Prot Limit Input X NORMAL/ALARM SPR PL