EXAMPLE 8 SERVICE2 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE
.
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
.
5. Scroll down to highlight SERVICE2.
6. Press SELECT
.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
OPTIONS BOARD 1
20 mA POWER CONFIGURATION
External = 0, Internal = 1
RESET 20 mA Power Source 0/1 DISABLE/ENABLE res 20 mA
0
DEMAND 20 mA Power Source 0/1 DISABLE/ENABLE dem 20 mA
0
SPARE ALERT ENABLE
Disable = 0, Low = 1, High = 2
Temp = Alert Threshold
CHWS Temp Enable 0-2 chws en
0
CHWS Temp Alert −40-245 (−40-118) DEG F (DEG C) chws al
245 (118)
CHWR Temp Enable 0-2 chwr en
0
CHWR Temp Alert −40-245 (−40-118) DEG F (DEG C) chwr al
245 (118)
Reset Temp Enable 0-2 rres en
0
Reset Temp Alert −40-245 (−40-118) DEG F (DEG C) rres al
245 (118)
Spare Temp 1 Enable 0-2 spr1 en
0
Spare Temp 1 Alert −40-245 (−40-118) DEG F (DEG C) spr1 al
245 (118)
Spare Temp 2 Enable 0-2 spr2 en
0
Spare Temp 2 Alert −40-245 (−40-118) DEG F (DEG C) spr2 al
245 (118)
Spare Temp 3 Enable 0-2 spr3 en
0
Spare Temp 3 Alert −40-245 (−40-118) DEG F (DEG C) spr3 al
245 (118)
OPTIONS BOARD 2
20 mA POWER CONFIGURATION
External = 0, Internal = 1
SPARE1 20 mA Power Source 0/1 DISABLE/ENABLE sp1 20 mA
0
SPARE2 20 mA Power Source 0/1 DISABLE/ENABLE sp2 20 mA
0
SPARE ALERT ENABLE
Disable = 0, Low = 1, High = 2
Temp = Alert Threshold
Spare Temp 4 Enable 0-2 spr4 en
0
Spare Temp 4 Alert −40-245 (−40-118) DEG F (DEG C) spr4 al
245 (118)
Spare Temp 5 Enable 0-2 spr5 en
0
Spare Temp 5 Alert −40-245 (−40-118) DEG F (DEG C) spr5 al
245 (118)
Spare Temp 6 Enable 0-2 spr6 en
0
Spare Temp 6 Alert −40-245 (−40-118) DEG F (DEG C) spr6 al
245 (118)
Spare Temp 7 Enable 0-2 spr7 en
0
Spare Temp 7 Alert −40-245 (−40-118) DEG F (DEG C) spr7 al
245 (118)
Spare Temp 8 Enable 0-2 spr8 en
0
Spare Temp 8 Alert −40-245 (−40-118) DEG F (DEG C) spr8 al
245 (118)
Spare Temp 9 Enable 0-2 spr9 en
0
Spare Temp 9 Alert −40-245 (−40-118) DEG F (DEG C) spr9 al
245 (118)
NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp Alert’’ threshold for each point listed. If the ‘Enable’’ is set to 1, a
value above the ‘‘Temp Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp Alert’’ threshold shall generate an alert
message. If the ‘‘Enable’’ is set to 0, alert generation is disabled.
EXAMPLE 9 SERVICE3 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE
.
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT
.
5. Scroll down to highlight SERVICE3.
DESCRIPTION CONFIGURABLE RANGE REFERENCE POINT NAME DEFAULT VALUE
Proportional Inc Band
5-10 gv inc
6.5
Proportional Dec Band
5-10 gv de
6.0
Proportional ECW Gain
1-3 gv ecw
2.0
EXAMPLE 10 MAINTENANCE (MAINT01) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE
.
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
.
5. Scroll down to highlight MAINT01.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
CAPACITY CONTROL
Control Point
0-120 (−17.8-48.9)
DEG F (DEG C)
ctript
Leaving Chilled Water
−40-245 (−40-118)
DEG F (DEG C)
LCW
Entering Chilled Water
−40-245 (−40-118)
DEG F (DEG C)
ECW
Control Point Error
−99-99 (−55-55)
DEG F (DEG C)
cperr
ECW Delta T
−99-99 (−55-55)
DEG F (DEG C)
ecwdt
ECW Reset
−99-99 (−55-55)
DEG F (DEG C)
ecwres
LCW Reset
−99-99 (−55-55)
DEG F (DEG C)
lcwres
Total Error + Resets
−99-99 (−55-55)
DEG F (DEG C)
error
Manual Slide Valve Count
−20-20 svt
Actual Slide Valve State
Increase, Hold, Decrease SV ACT
Proportional Inc Band
5-10 sv inc
6.5
Proportional Dec Band
5-10 sv dec
6.0
Proportional ECW Gain
1-3 sv ecw
2.0
Water/Brine Deadband
0.5-2 (0.3-1.1)
DEG F (DEG C)
cwdb 1.0 (.5)
NOTE: Overriding shall not be supported on this maintenance screen. Active overriding shall show the associated point in alert (!). Only values with capital letter reference