Shutdown Sequence Shutdown of the machine can
occur if any of the following events happen:
the STOP button is pressed for at least one second (the
alarm light will blink once to confirm stop command)
recycle condition is present (see Chilled Water Recycle Mode
section)
time schedule has gone into UNOCCUPIED mode (ma-
chine protective limit has been reached and machine is in
alarm)
the start/stop status is overridden to stop from the CCN
network or the LID
When a stop signal occurs, the shutdown sequence first
stops the compressor by deactivating the start relay. The slide
valve decrease timer is activated for 3 minutes to open the
slide valve. The condenser water pump relay is shut down
30 seconds after the compressor run contact is open and mo-
tor load is less than 10%. The service ontime and compres-
sor ontime timers are deactivated. The 3-minute stop-
to-start timer will now begin to count down. If the
15-minute start-to-start timer is still greater than 3 minutes,
then this time is now displayed. Last, the chilled water/brine
pump is shut down.
Certain conditions during shutdown will change this
sequence:
if the COMPRESSOR MOTOR LOAD is greater than 10%
after shutdown, or the starter contacts remain energized,
the chilled water pump and the condenser water pump re-
main energized and the alarm is displayed
if the ENTERING CONDENSER WATER temperature is
less than 115 F (46 C) [125 F (52 C)] and the condenser
refrigerant temperature is less than the CONDENSER
FREEZE POINT plus 5°F(3°C)atshutdown, the Con-
denser Pump Control algorithm will determine when the
condenser pump will be deenergized after shutdown
if the machine shuts down due to low refrigerant tempera-
ture, the chilled water pump will stay running until the
LEAVING CHILLED WATER is greater than CONTROL
POINT, plus F (3° C).
Automatic Soft Stop Amps Threshold (PSIO Soft-
ware Version 13 and Higher)
The SOFT STOP
AMPS THRESHOLD unloads the slide valve of the com-
pressor automatically when a non-recycle, non-alarm stop
signal is emitted before the compressor motor is
deenergized.
If the STOP button is pressed, the slide valve unloads to
a preset amperage percent. Then, the compressor will shut
off.
If the machine enters an Alarm state or if the compressor
enters a RECYCLE mode, the compressor will be de-
energized immediately.
To activate SOFT STOP AMPS THRESHOLD, view the
bottom of Service1 screen. Set the Soft Stop Amps Thresh-
old value to the percentage amps that the slide valve will
achieve the motor will be shut down. The default setting is
100% (no Soft Stop).
When the SOFT STOPAMPS THRESHOLD is being ap-
plied, a status message ‘SHUTDOWN IN PROGRESS, COM-
PRESSOR UNLOADING’ is shown.
Chilled Water Recycle Mode When the compres-
sor is running in a lightly loaded condition, the machine may
cycle off and wait until the load increases before restarting.
This cycling of the chiller is normal and is known as re-
cycle. A recycle shutdown is initiated when any of the fol-
lowing conditions are present:
when in LCW control, the LEAVING CHILLED WATER
temperature is more than F (3° C) below the control
point, and the CONTROL POINT has not increased in the
last 5 minutes
when ECW CONTROL OPTION is enabled, the ENTER-
ING CHILLED WATER temperature is more than F (3°
C) below the CONTROL POINT, and the CONTROL POINT
has not increased in the last 10 minutes
when the LEAVING CHILLED WATER temperature is within
F (2° C) of the BRINE REFRIG TRIPPOINT
A—START INITIATED: Pre-start checks are made; evaporator
pump started
B—Condenser water pump started (5 seconds after A)
C—Water flows verified (30 seconds to 5 minutes maximum)
D—Chilled water temperature checked against control point;
tower fan control enabled; slide valve decrease timer checked
to verify slide valve position
E—Refrigerant type verified (up to 3 minutes after D).
F—Compressor motor starts; phase reversal conditions moni-
tored; compressor ontime and service ontime start;
15-minute inhibit timer starts (10 seconds after E)
G—Shutdown initiated: Compressor motor stops; compressor
ontime and service ontime stop; 3-minute inhibit timer starts
on PSIO Software Version 8 and 12 and 1-minute inhibit
timer on PSIO Software Version 13 and higher; slide valve
decrease activated for 1 minute
H—Evaporator pump deenergized (30 seconds after G); con-
denser pump and tower fan control may continue to oper-
ate if condenser pressure is high; evaporator pump may
continue if in RECYCLE mode
I—Slide valve decrease timer expires (3 minutes after G)
O/A Restart permitted (both inhibit timers expired) (minimum of
15 minutes after F; minimum of 1 minute after G)
Fig. 28 Control Sequence