Table 3 LID Screens (cont)
EXAMPLE 11 MAINTENANCE (MAINT02) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE
.
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
.
5. Scroll down to highlight MAINT02.
6. Press SELECT
.
DESCRIPTION CONFIGURABLE RANGE UNITS REFERENCE POINT NAME DEFAULT VALUE
OVERRIDE/ALERT STATUS
MOTOR WINDING TEMP −40-245 (−40-118) DEG F (DEG C) MTRW
Override Threshold 150-200 (66-93) DEG F (DEG C) mt over
200 (93)
CONDENSER PRESSURE 0-420 (0-2896) PSI (kPa) CRP
Override Threshold 150-250 (1034-1724) PSI (kPa) cp over
230 (1586)
EVAPORATOR REFRIG TEMP −40-245 (−40-118) DEG F (DEG C) ERT
Override Threshold 2-45 (1-7.2) DEG F (DEG C) rt over
35 (1.7)
DISCHARGE TEMPERATURE −40-245 (−40-118) DEG F (DEG C) CMPD
Alert Threshold 170-200 (76.7-93.3) DEG F (DEG C) cd alert
200 (93.3)
OIL FILTER PRESSURE DROP 0-120 (0-827) PSID (kPad) oil fltr
Alert Threshold 15-90 (103-621) PSID (kPad) oil alrt 30 (207)
NOTES:
1. Overriding shall not be supported on this maintenance screen. Active overrides shall show the associated point in alert (!). Only values with capital
letter reference point names shall be variables available for read operation.
2. Values in [ ] indicate HFC-134a values.
EXAMPLE 12 MAINTENANCE (MAINT03) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE
.
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
.
5. Scroll down to highlight MAINT03.
6. Press SELECT
.
DESCRIPTION STATUS UNITS REFERENCE POINT NAME
Hot Gas Bypass ACTIVE ? NO/YES
Active Delta P 0-200 (0-1379) PSI (kPa) dp a
Active Delta T 0-200 (0-111) DEG F (DEG C) dt a
Calculated Delta T 0-200 (0-111) DEG F (DEG C) dt c
NOTE: Overriding shall not be supported on this maintenance screen. Active overrides shall show the associated point in alert (*). Only values with
capital letter reference point names shall be variables available for read operation.
EXAMPLE 13 MAINTENANCE (MAINT04) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press MENU
.
2. Press SERVICE
.
3. Scroll down to highlight CONTROL ALGORITHM STATUS.
4. Press SELECT
.
5. Scroll down to highlight MAINT04..
6. Press SELECT
.
DESCRIPTION STATUS UNITS REFERENCE POINT NAME
LEAD/LAG: Configuration DISABLE,LEAD,LAG,STANDBY leadlag
Current Mode DISABLE,LEAD,LAG,STANDBY llmode
Load Balance Option DISABLE/ENABLE loadbal
LAG Start Time 0-99 MIN lagstart
LAG Stop Time 0-99 MIN lagstop
Prestart Fault Time 0-30 MIN preflt
Pulldown: Delta T/Min x.xx D DEG pull dt
Satisfied? 0/1 NO/YES pull sat
LEAD CHILLER in Control 0/1 NO/YES leadctrl
LAG CHILLER: Mode Reset,Off,Local,CCN lagmode
Run Status
Timeout,Recycle,Startup,Ramping,Running
Demand,Override,Shutdown,Abnormal,Pumpdown
lagstat
Start/Stop Stop,Start,Retain lag s s
Recovery Start Request No/Yes lag rec
STANDBY CHILLER: Mode Reset,Off,Local,CCN stdmode
Run Status
Timeout,Recycle,Startup, Ramping,Running
Demand,Override,Shutdown,Abnormal,Pumpdown
stdstat
Start/Stop Stop,Start,Retain std s s
Recovery Start Request No/Yes std rec
NOTES:
1. Overriding shall not be supported on this maintenance screen.
2. D =delta degrees.