Table 10 LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
I. NORMAL RUN OVERRIDES ACTIVE (ALERTS)
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
RUN CAPACITY LIMITED HIGH CONDENSER PRESSURE CRP VALUE exceeded limit of [LIMIT]*.
Condenser pressure override.
See Capacity Overrides, Table 5.
Correct operating condition.
RUN CAPACITY LIMITED HIGH MOTOR TEMPERATURE MTRW VALUE exceeded limit of [LIMIT]*.
Motor temperature override.
RUN CAPACITY LIMITED LOW EVAP REFRIG TEMP ERT VALUE exceeded limit of [LIMIT]*.
Check refrigerant charge level.
RUN CAPACITY LIMITED MANUAL SLIDE VALVE SV MAN Run Capacity Limited: Manual
slide valve control.
*[LIMIT] is shown on the LID as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert.
J. OUT-OF-RANGE SENSOR FAILURES
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
SENSOR FAULT LEAVING CHW TEMPERATURE Sensor Fault: Check leaving CHW
sensor.
See sensor test procedure and check
sensors for proper operation and
wiring.
SENSOR FAULT ENTERING CHW TEMPERATURE Sensor Fault: Check entering CHW
sensor.
SENSOR FAULT CONDENSER PRESSURE Sensor Fault: Check cond pressure
transducer.
SENSOR FAULT EVAPORATOR PRESSURE Sensor Fault: Check evap pressure
transducer.
SENSOR FAULT MOTOR WINDING TEMP Sensor Fault: Check motor temp sensor.
SENSOR FAULT ROTOR INLET TEMPERATURE Sensor Fault: Check rotor inlet temp
sensor.
SENSOR FAULT OIL SUMP TEMPERATURE Sensor Fault: Check oil sump temp
sensor.
SENSOR FAULT OIL PRESSURE TRANSDUCER Sensor Fault: Check oil pressure
transducer.
74