Carrier 23XL Especificações Página 58

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 104
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 57
OPERATING INSTRUCTIONS
Operator Duties
1. Become familiar with refrigeration machine and related
equipment before operating the machine.
2. Prepare the system for start-up, start and stop the ma-
chine, and place the system in a shutdown condition.
3. Maintain a log of operating conditions and recognize any
abnormal readings.
4. Inspect the equipment, make routine adjustments, and per-
form a Control Test. Maintain the proper oil and refrig-
erant levels.
5. Protect the system from damage during shutdown
periods.
6. Maintain set point, time schedules, and other PIC
functions.
Prepare the Machine for Start-Up Follow the
steps described in the Initial Start-Up section on page 56.
To Start the Machine
1. Start the water pumps, if not automatic.
2. On the LID default screen, press the LOCAL
or
CCN
softkey to start the system. If the machine is in
the OCCUPIED mode, and all machine timers have ex-
pired, the start sequence will start. Follow the procedure
described in the Start-Up/Shutdown/Recycle section on
page 37.
Check the Running System After the compres-
sor starts, the operator should monitor the LID display and
observe the parameters for normal operating conditions:
1. The oil sump temperature should be 20-40 F (11-20 C)
above the condenser refrigerant temperature. At start-up,
the oil sump temperature will rapidly decrease. It will then
slowly rise to the compressor discharge temperature. Af-
ter start-up, the minimum oil sump temperature should
be 20 F (11 C) above the condenser refrigerant tempera-
ture. The oil sump temperature is dependent upon the com-
pressor discharge refrigerant temperature.
2. When the compressor is running, the oil sump should be
at least
3
4
full. The liquid level should be visible in the
separator sight glass.
3. The oil pressure displayed on the LID default screen is
equal to the difference between the oil pressure and evapo-
rator pressure transducer readings. Both readings are shown
on the Status01 table. Typically the reading will be 4 to
20 psi (28 to 138 kPa) [1.4 to 7 psi (9.7 to
48.3 kPa)] at initial start up until oil pressure ramp
up is complete. The full load reading is approximately
120 psi (821 kPa) [78 psi (538 kPa)].
4. The moisture indicator (dry-eye) sight glass on the re-
frigerant motor cooling line should indicate refrigerant
flow and a dry condition.
5. The condenser pressure and temperature varies with the
machine design conditions. Typically the pressure will range
between 100 and 210 psig (690 to 1450 kPa)
[60 to 135 psig (329 to 780 kPa)] with a corresponding
temperature range of 60 to 105 F (15 to 41 C). The con-
denser entering water temperature should be controlled
below the specified design entering water temperature to
save on compressor kilowatt requirements but, not be be-
low 55 F (12.8 C).
6. Cooler pressure and temperature also will vary with the
design conditions. Typical pressure range will be be-
tween 60 and 80 psig (410 and 550 kPa) [30 to 40 psig
(204 to 260 kPa)] with temperature ranging between
34 and 45 F (1 and 8 C).
7. The compressor may operate at full capacity for a short
time after the pulldown ramping has ended, even though
the building load is small. The active electrical demand
setting can be overridden to limit the compressor IKW
(input kilowatt), or the pulldown rate can be decreased to
avoid a high demand charge for the short period of high
demand operation. Pulldown rate can be based on load
rate or temperature rate. It is accessed on the Equipment
Configuration menu Config table (Table 3,
Example 5).
To Stop the Machine
1. The occupancy schedule will start and stop the machine
automatically once the time schedule is set up.
2. By pressing the Stop button for one second, the alarm
light will blink once to confirm that the button has been
pressed. Then the compressor will follow the normal shut-
down sequence as described in the Controls section
page 13. The machine will not restart until the CCN
or
LOCAL
softkey is pressed. The machine is now in the
OFF mode.
If the machine fails to stop, in addition to action that the
PIC will initiate, the operator should open the slide valve
to reduce machine load by overriding the slide valve count
to −20. Then, the operator should open the main discon-
nect.
Do not attempt to stop the machine by opening an iso-
lating knife switch. High intensity arcing may occur. Do
not restart the machine until the problem is diagnosed
and corrected.
After Limited Shutdown No special preparations
should be necessary. Follow the regular preliminary checks
and starting procedures.
Extended Shutdown The refrigerant should be trans-
ferred into the storage vessel (if supplied; see Pumpout and
Refrigerant Transfer Procedures) in order to reduce machine
pressure and possibility of leaks. Maintain a holding charge
of 5 to 10 lbs (2.27 to 4.5 kg) of refrigerant to prevent air
from leaking into the machine.
If freezing temperatures are likely to occur in the machine
area, drain the chilled water, condenser water, and the pum-
pout condenser water circuits to avoid freeze-up. Keep the
waterbox drains open.
Leave the oil charge in the machine with the oil heater (if
applicable) and controls energized to maintain the minimum
oil sump temperature.
After Extended Shutdown Be sure that the water
system drains are closed. It may be advisable to flush the
water circuits to remove any soft rust which may have formed.
This is a good time to brush the tubes if necessary.
Check the cooler pressure on the LID default screen, and
compare to the original holding charge that was left in the
machine. If (after adjusting for ambient temperature changes)
any loss in pressure is indicated, check for refrigerant leaks.
See Check Machine Tightness section, page 39.
Recharge the machine by transferring refrigerant from the
storage tank (if supplied). Follow the Pumpout and Refrig-
erant Transfer Procedures section. Observe freeze-up
precautions.
58
Vista de página 57
1 2 ... 53 54 55 56 57 58 59 60 61 62 63 ... 103 104

Comentários a estes Manuais

Sem comentários